 Catalog 1308242 Issued 3-03
AGASTAT
2100 series
Miniature Electropneumatic Timing Relay
Users should thoroughly review the technical data before selecting a product part number. It is recommended that users also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application.
Design Features
* High Repeat Accuracy over voltage and temperature extremes * Hermetically sealed units are designed for high shock and vibration applications * Instant recycling - easy linear adjustment * Exclusive Dial Head adjustment - no needle valves * Delay ranges from milliseconds to 3 minutes * DPDT contacts
Repeat Accuracy: NORMAL VERTICAL POSITION +5% at 25C; +7% at 85C; +8% at -55C. The average time between -55C and 85C will be within +20% of the average @ 25C with a proportionally reduced effect at lesser extremes. In extremely short delay settings an additional 8 msec. variation may result on AC models due to "half cycle" alternating current effect. Setting Tolerance: Factory time setting, when specified, subject to additional +5% tolerance. Position Sensitivity: HORIZONTAL POSITION: Approximately 5% increase from the initial time in the vertical position. INVERTED POSITION: Approximately 10% increase from the initial time in the vertical position. Reset Time: 2112 Series: 25 msec.; 2122 Series: 75 msec. Relay Release Time: 25 msec. (2112 Series) Relay Operate Time: 75 msec. (2122 Series) Operating Voltage: Coil Data Nominal Resistance Operating Ohms Code Voltage 10% M N P R Y 12VDC 28VDC 48VDC 110VDC 125VDC 30 131 500 3200 3380 Nominal Operating Voltage Resistance Ohms 10%
Design & Construction
Sealed patented timing head circulates air under controlled pressure through a variable orifice to provide adjustable timing. Circular-path Dial Head principle replaces traditional needle valve. Snap-action switch assembly provides sustained contact pressure during timing cycles. Specially designed over center mechanism assures flutterfree load transfer after extended delay periods. Precision-wound solenoid assembly supplies the basic motive force when the control circuit is closed. These assemblies are mounted in a rigid self-supporting framework within a steel enclosure. This rugged construction assures permanent alignment of all operating members, the key to this unit's long trouble-free operation.
Code S S T U
Operation
Series 2112 (On-Delay) - Applying rated voltage to the solenoid coil starts the preset time delay. At the end of the delay period the NC contacts break and the NO contacts make. Contacts remain in this position until the coil is deenergized, when the switch instantaneously returns to its original position. De-energizing the coil, either during or after the delay period, will immediately (within 25 msec.) recycle the unit. It will then provide another full delay period on re-energization. Series 2122 (Off-Delay) - Applying rated voltage to the coil for at least 75 msec. (for accurate timing) will instantaneously transfer the switch, breaking the NC contacts and making the NO contacts. Contacts remain in this position as long as the coil is energized. The preset time delay period begins as soon as the coil is de-energized, at the end of which the switch returns to its original position. No power is required during the timing period. Reenergizing the coil, either during or after the delay period, will immediately start a new cycle with full delay period.
120V 60 Hz 190 (2112 Series) 120V 60Hz 285 (2122 Series) 240V 60Hz 765 115V 400Hz 2600
Transients: Insensitive to transients of +1500 VAC for 10 milliseconds Dielectric: 1000V RMS @ 60Hz between non-connected terminals. Contact Rating (DPDT Contacts): 30V DC Inductive (Amps) Resistive (Amps) 2 10 110V DC .75 1 120V 60Hz 3 10 120V 400Hz 2 10 240V 60Hz 1.5 5
Based on 100,000 operations electrical, 1,000,000 mechanical. Inductive and capacitive load should not have inrush currents that exceed five times normal operating load. Ambient Temperature Range: -55C to +85C Weight: Maximum, any unit - 17 ozs. Mounting/Terminals: Chassis mounting tabs, octal plugs and external (-4) or internal (-5) adjustment. Panel mounting back plate, internal adjustment, and solder hook terminals (-9).
Operation (Listed values at nom. voltage, 25C unless noted).
Operating Mode: 2112: On-delay (delay on pull-in); 2122: Off-delay (delay on drop-out) Timing Adjustment: All standard models offer easy linear adjustment over one of nine timing ranges listed below. For applications requiring frequent readjustment, the external knob model with calibrated dial is recommended. For tamper-proof installation or where readjustment is infrequent, the internal key model may be preferred. This model requires removal of the cover plate for timing adjustment. Hermetically sealed models provide a slotted adjusting screw under the cap nut on the top cover. Timing Ranges: Code A B C D E F Range .03 to .1 sec. .1 to .3 sec. .15 to 1.0 sec. .375 to 3.0 sec. .75 to 10.0 sec. 1.0 to 30.0 sec. Code G H J K L Range 2.0 to 60.0 sec. 5.0 to 120.0 sec. 5.0 to 180.0 sec. 1.5 to 30.0 cycles 3.0 to 120.0 cycles
--4
--5
--9
These are minimum standards; where more severe environmental conditions must be met, please consult the factory.
Dimensions are shown for
1254 reference purposes only.
Dimensions are in inches over (millimeters) unless otherwise specified.
Specifications and availability subject to change.
www.tycoelectronics.com Technical support: Refer to inside back cover.
Catalog 1308242 Issued 3-03
AGASTAT
Outline Dimensions for Industrial Models (Dimensions in inches. Multiply by 25.4 to obtain millimeters.)
Ordering Information for Industrial Models
Typical Part No.
21
1
2
D
4
N
B
1. Basic Series: 21 = 2100 Miniature electropneumatic timing relay 2. Operation: 1 = On-delay 2 = Off-delay 3. Contact Arrangement: 2 = DPDT (2 form C) 4. Operating Voltage: A = AC D = DC 5. Physical Characteristics: Code Enclosure Adjustment Connector Mounting 4= Unsealed External Knob Octal Plug Chassis Mount 5= Unsealed Internal Key Octal Plug Chassis Mount 9= Unsealed Internal Key Solder Hook Panel Mount Plate 6. Coil Voltage: M = 12VDC N = 28VDC P = 48VDC R = 110VDC Y = 125VDC S = 120VAC, 50/60 Hz. T = 240VAC, 60 Hz. 7. Timing Range: A = .03 to .1 sec. C = .15 to 1.0 sec. E = .75 to 10.0 sec. H = 5.0 to 120.0 sec. K = 1.5 to 30.0 cycles B = .1 to .3 sec. D = .375 to 3.0 sec. F = 1.0 to 30.0 sec. J = 5.0 to 180.0 sec. L = 3.0 to 120.0 cycles
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..
None at present.
Dimensions are shown for reference purposes only.
Dimensions are in inches over (millimeters) unless otherwise specified.
Specifications and availability subject to change.
www.tycoelectronics.com Technical support: 1255 Refer to inside back cover.
Catalog 1308242 Issued 3-03
AGASTAT
Specifications for MIL-Spec and Hermetically Sealed Models
Dielectric: In accordance with specification MIL-R6106E (ASG). Also withstands 1,000 Volts RMS at 60 Hz between non-connected terminals. Other: Agastat Miniature Timing Relays also conform to applicable Mil-Spec. requirements covering: Moisture Ozone Humidity Sunshine Sand/Dust Acoustic Noise Salt Spray Prolonged Storage
Agastat timing relays perform to military specifications in Patriot missiles.
Outline Dimensions for MIL-Spec and Hermetically Sealed Models (In inches. Multiply by 25.4 for millimeters).
8 pin solder hook or MS/AN Connector
8 pin solder hook or MS/AN Connector
Panel Mount --H1, --H3
Panel Mount --9
Octal Plug (with internal adjustment or external adjustment knob
Octal Plug (with internal adjustment or external adjustment knob
Chassis Mount --H2
Chassis Mount --4, --5
Ordering Information for MIL-Spec and Hermetically Sealed Models
Typical Part No.
21
1
2
D
H1
N
B
1. Basic Series: 21 = 2100 Miniature electropneumatic timing relay 2. Operation: 1 = On-delay 2 = Off-delay 3. Contact Arrangement: 2 = DPDT (2 form C) 4. Operating Voltage: A = AC D = DC 5. Physical Characteristics: Code Enclosure Adjustment Connector Mounting H1 = Hermetically Sealed External Screw Solder Hook Panel Mount Plate H2 = Hermetically Sealed External Screw Octal Plug Chassis Mount H3 = Hermetically Sealed External Screw "AN" Connector Panel Mount Plate 4= Unsealed External Knob Octal Plug Chassis Mount 5= Unsealed Internal Key Octal Plug Chassis Mount 9= Unsealed Internal Key Solder Hook Panel Mount Plate 6. Coil Voltage: M = 12VDC N = 28VDC P = 48VDC R = 110VDC Y = 125VDC S = 120VAC, 50/60 Hz. T = 240VAC, 60 Hz. U = 115VAC, 400 Hz. 7. Timing Range: A = .03 to .1 sec. C = .15 to 1.0 sec. E = .75 to 10.0 sec. H = 5.0 to 120.0 sec. K = 1.5 to 30.0 cycles B = .1 to .3 sec. D = .375 to 3.0 sec. F = 1.0 to 30.0 sec. J = 5.0 to 180.0 sec. L = 3.0 to 120.0 cycles
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery..
None at present.
Dimensions are shown for
1256 reference purposes only.
Dimensions are in inches over (millimeters) unless otherwise specified.
Specifications and availability subject to change.
www.tycoelectronics.com Technical support: Refer to inside back cover.


▲Up To Search▲   

 
Price & Availability of 2112A9NA

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X